Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
' #"(' '%#( ' && # #" ' ("'#" #+ &
(% #""' ' +$#& #"(' *%& '# ' #%%&$#""
#!$%&&#" '%!" & & ' # #*" ' '" ' #!$%&&#"
'%!" & *' &%*%)%
)#' ' %$' (% #(' # ' *, $ ( '
$ (%$' #""'#% "'# ' %$' #" ' %%
$" & (% #" $ #% (% #" $ *&' '
#""'#% " $
Mounting Holes
Plug/Receptacle
UPS Connector
Three Foot Cord
Terminal Block
Access Hole
for Conduit
Power Cable Terminations Tightening Torque
Wire Function Terminal
Position
Terminal Wire
Size Rating*
Entrelec Phoenix
Contact
REPO
L1 TB1Ć4
L2 TB1Ć5
12Ć22 AWG
(4Ć0 mm
2
)
3.5 - 5.3 lb/in 5.6 - 6.8 lb/in
Ground
TB1Ć6
*Suggested wire size is #18ĆAWG (0.75 mm
2
)75_C copper wire minimum.
NOTE: The REPO function activates when L1 and L2 are shorted together.